Factory-direct manufacturer · Xiamen, China · Exporting worldwide

Flow Sensors & Switches

HSM30 Digital Thermal Flow Switch

LED display

Request a quote

HSM30 technical data

Measurement

Measuring range — water
3–300 cm/s
Measuring range — oil
3–300 cm/s
Measuring range — gas
200–3000 cm/s
Maximum pressure
100 bar
Temperature gradient
Max. 250 K/min
Thermal response time
≤ 12 s

Electrical

Supply voltage
DC 24 V / AC-DC 110 V / AC-DC 220 V
Current consumption
< 80 mA
Output
Relay, PNP, NPN or 4–20 mA (specify at order)
Display
Four-digit LED
Configuration
Two front-panel keys
Protection
Reverse polarity, short circuit, overload
Switch timing
ON typ. 2 s (1–13 s); OFF typ. 2 s (1–15 s)

Mechanical

Wetted material
SUS 316L
Process connection
G1/2″ standard, others to order
Medium temperature
−20 to +100 °C
Ingress protection
IP67

Values are for the standard configuration. Ranges, threads, probe lengths and output types outside this table are available on request — the datasheet revision for a custom build is issued with the quotation.

Request the PDF datasheet →

Flow Sensors & Switches

HSM30Digital Thermal Flow Switch

LED display

Thermal flow switch with a four-digit LED display showing live flow velocity, set by two front-panel keys rather than a screwdriver. Reverse-polarity, short-circuit and overload protected. Handles media up to 100 °C and pressures to 100 bar, sealed to IP67.

Engineering reply · Evaluation samples available · Custom ranges built to order

  • Live four-digit LED display of flow velocity
  • Two-key set-point entry — no screwdriver, no guessing
  • Reverse-polarity, short-circuit and overload protection
  • Medium temperature up to 100 °C
  • Relay, PNP, NPN or 4–20 mA output

How it works

The HSM30 replaces the potentiometer with a digital display and a two-key interface. Instead of guessing at a screw position, the maintenance technician reads the actual velocity on the LED display, presses the key when the flow is at the value they want, and the trip point is stored. That makes commissioning repeatable across several identical machines, and it makes fault-finding possible without a separate flow meter: if the pump is running and the display reads zero, the problem is upstream. The electronics include reverse-polarity, short-circuit and overload protection, which is the difference between a blown fuse and a dead instrument on a badly wired panel. It also extends the medium temperature ceiling to 100 °C, above the 80 °C limit of the analogue models.

Typical applications

  • Machines where commissioning must be identical across many units
  • Plant rooms where operators need to read flow without a control system
  • Cooling circuits on lasers, spindles and power supplies
  • Water-treatment dosing lines

Not certain HSM30 is the right unit?