Flow Sensors & Switches
HSM30 Digital Thermal Flow Switch
LED display

HSM30 technical data
Measurement
- Measuring range — water
- 3–300 cm/s
- Measuring range — oil
- 3–300 cm/s
- Measuring range — gas
- 200–3000 cm/s
- Maximum pressure
- 100 bar
- Temperature gradient
- Max. 250 K/min
- Thermal response time
- ≤ 12 s
Electrical
- Supply voltage
- DC 24 V / AC-DC 110 V / AC-DC 220 V
- Current consumption
- < 80 mA
- Output
- Relay, PNP, NPN or 4–20 mA (specify at order)
- Display
- Four-digit LED
- Configuration
- Two front-panel keys
- Protection
- Reverse polarity, short circuit, overload
- Switch timing
- ON typ. 2 s (1–13 s); OFF typ. 2 s (1–15 s)
Mechanical
- Wetted material
- SUS 316L
- Process connection
- G1/2″ standard, others to order
- Medium temperature
- −20 to +100 °C
- Ingress protection
- IP67
Values are for the standard configuration. Ranges, threads, probe lengths and output types outside this table are available on request — the datasheet revision for a custom build is issued with the quotation.
Request the PDF datasheet →Flow Sensors & Switches
HSM30Digital Thermal Flow Switch
LED display
Thermal flow switch with a four-digit LED display showing live flow velocity, set by two front-panel keys rather than a screwdriver. Reverse-polarity, short-circuit and overload protected. Handles media up to 100 °C and pressures to 100 bar, sealed to IP67.
Engineering reply · Evaluation samples available · Custom ranges built to order
- Live four-digit LED display of flow velocity
- Two-key set-point entry — no screwdriver, no guessing
- Reverse-polarity, short-circuit and overload protection
- Medium temperature up to 100 °C
- Relay, PNP, NPN or 4–20 mA output
How it works
The HSM30 replaces the potentiometer with a digital display and a two-key interface. Instead of guessing at a screw position, the maintenance technician reads the actual velocity on the LED display, presses the key when the flow is at the value they want, and the trip point is stored. That makes commissioning repeatable across several identical machines, and it makes fault-finding possible without a separate flow meter: if the pump is running and the display reads zero, the problem is upstream. The electronics include reverse-polarity, short-circuit and overload protection, which is the difference between a blown fuse and a dead instrument on a badly wired panel. It also extends the medium temperature ceiling to 100 °C, above the 80 °C limit of the analogue models.
Typical applications
- Machines where commissioning must be identical across many units
- Plant rooms where operators need to read flow without a control system
- Cooling circuits on lasers, spindles and power supplies
- Water-treatment dosing lines
Not certain HSM30 is the right unit?
Send the medium, range, process connection and the signal your control system accepts. We will confirm the model — or tell you which one fits better — before you commit to an order.
Same family
Other flow instruments
Illustrative imageThermal Flow Switch
Single set-point
Thermal-dispersion flow switch with a single adjustable set-point, sealed all-in-one stainless body rated IP67 and 100 bar. Relay, PNP, NPN or 4–20 mA output, G1/2 thread as standard. No paddle and no moving part in the flow path, so scale and debris cannot jam it.
View specifications
Illustrative imageThermal Flow Switch
Dual set-point
Two independently adjustable set-points on one thermal flow switch, giving alarm and trip from a single instrument. Two potentiometers set the thresholds; red, yellow and green LEDs report which band the flow is in. IP68 sealed body, relay or PNP/NPN output, rated to 100 bar.
View specifications
Mass Flow Controller
Closed loop, 100–200 L/min
Closed-loop gas flow controller combining a thermal flow sensor and a normally-closed solenoid valve in one body. Three ranges — 100, 150 and 200 L/min — with ±1 % FS accuracy, 2 s response and 5–100 % control range. Swagelok or VCR fittings, ±15 V DC supply.
View specifications