Flow Sensors & Switches
HSM10 Thermal Flow Switch
Single set-point

HSM10 technical data
Measurement
- Measuring range — water
- 0–5 m/s
- Measuring range — oil
- 0–10 m/s
- Measuring range — gas
- 0–20 m/s
- Maximum pressure
- 100 bar
- Temperature gradient
- Max. 250 K/min
- Thermal response time
- ≤ 12 s
Electrical
- Supply voltage
- DC 24 V / AC-DC 110 V / AC-DC 220 V
- Current consumption
- < 80 mA
- Output
- Relay, PNP, NPN or 4–20 mA (specify at order)
- Switch timing
- ON typ. 2 s (1–13 s); OFF typ. 2 s (1–15 s)
- Indication
- 6 LEDs; red = below set-point, yellow = at or above set-point
Mechanical
- Wetted material
- SUS 316L
- Process connection
- G1/2″ standard, others to order
- Medium temperature
- −20 to +80 °C (high-temperature version available)
- Ingress protection
- IP67
Values are for the standard configuration. Ranges, threads, probe lengths and output types outside this table are available on request — the datasheet revision for a custom build is issued with the quotation.
Request the PDF datasheet →Flow Sensors & Switches
HSM10Thermal Flow Switch
Single set-point
Thermal-dispersion flow switch with a single adjustable set-point, sealed all-in-one stainless body rated IP67 and 100 bar. Relay, PNP, NPN or 4–20 mA output, G1/2 thread as standard. No paddle and no moving part in the flow path, so scale and debris cannot jam it.
Engineering reply · Evaluation samples available · Custom ranges built to order
- No moving parts in the flow path — unaffected by debris and scale
- All-in-one sealed construction, fully waterproof
- Low thermal drift, so the set-point stays where you put it
- Relay, PNP, NPN and 4–20 mA output options
- Treated probe resists fouling in poor-quality water
How it works
The HSM10 detects flow by heating a probe slightly above the medium temperature and measuring how quickly that heat is carried away. Moving liquid or gas removes heat faster than a still column, so the electronics can decide whether the pipe is flowing and trip a relay at your set-point. Because the sensing element is a solid stainless probe with no paddle, vane or orifice, there is nothing for scale, sludge or debris to block. The probe face receives a surface treatment that resists the corrosion and fouling that shorten the life of ordinary flow switches in poor-quality water. Once the trip point is set, the unit holds it without periodic adjustment, which matters on plant that cannot tolerate an instrument drifting out of calibration.
Ordering notes
- Set-point is fixed at the factory to your stated velocity unless you ask for field adjustability.
- For sanitary or aggressive media, specify the probe material and thread at the time of enquiry.
Typical applications
- Pump dry-run protection on water and coolant loops
- Cooling-water flow confirmation on welders, furnaces and induction heaters
- Lubrication and hydraulic circuit monitoring
- Boiler feedwater and condensate lines
- HVAC chilled-water and hot-water branches
Not certain HSM10 is the right unit?
Send the medium, range, process connection and the signal your control system accepts. We will confirm the model — or tell you which one fits better — before you commit to an order.
Same family
Other flow instruments
Illustrative imageThermal Flow Switch
Dual set-point
Two independently adjustable set-points on one thermal flow switch, giving alarm and trip from a single instrument. Two potentiometers set the thresholds; red, yellow and green LEDs report which band the flow is in. IP68 sealed body, relay or PNP/NPN output, rated to 100 bar.
View specifications
Illustrative imageDigital Thermal Flow Switch
LED display
Thermal flow switch with a four-digit LED display showing live flow velocity, set by two front-panel keys rather than a screwdriver. Reverse-polarity, short-circuit and overload protected. Handles media up to 100 °C and pressures to 100 bar, sealed to IP67.
View specifications
Mass Flow Controller
Closed loop, 100–200 L/min
Closed-loop gas flow controller combining a thermal flow sensor and a normally-closed solenoid valve in one body. Three ranges — 100, 150 and 200 L/min — with ±1 % FS accuracy, 2 s response and 5–100 % control range. Swagelok or VCR fittings, ±15 V DC supply.
View specifications