Flow Sensors & Switches
HSM20 Thermal Flow Switch
Dual set-point

HSM20 technical data
Measurement
- Measuring range — water
- 0–5 m/s
- Measuring range — oil
- 0–10 m/s
- Measuring range — gas
- 0–20 m/s
- Maximum pressure
- 100 bar
- Temperature gradient
- Max. 250 K/min
- Thermal response time
- ≤ 12 s
Electrical
- Supply voltage
- DC 24 V / AC-DC 110 V / AC-DC 220 V
- Current consumption
- < 80 mA
- Output
- Relay, or PNP / NPN — two channels selectable
- Adjustment
- Dual potentiometer
- Switch timing
- ON typ. 2 s (1–13 s); OFF typ. 2 s (1–15 s)
- Indication
- Red = below set-point 1; yellow = above set-point 1; green = above set-point 2
Mechanical
- Wetted material
- SUS 316L
- Process connection
- G1/2″ standard, others to order
- Medium temperature
- −20 to +80 °C (high-temperature version available)
- Ingress protection
- IP68
Values are for the standard configuration. Ranges, threads, probe lengths and output types outside this table are available on request — the datasheet revision for a custom build is issued with the quotation.
Request the PDF datasheet →Flow Sensors & Switches
HSM20Thermal Flow Switch
Dual set-point
Two independently adjustable set-points on one thermal flow switch, giving alarm and trip from a single instrument. Two potentiometers set the thresholds; red, yellow and green LEDs report which band the flow is in. IP68 sealed body, relay or PNP/NPN output, rated to 100 bar.
Engineering reply · Evaluation samples available · Custom ranges built to order
- Two independent set-points — warning and trip from one probe
- Dual potentiometer adjustment, set accurately in the field
- Three-colour LED band indication readable at a distance
- IP68 sealed body for washdown and wet locations
- Upgrade path from conventional single-point flow switches
How it works
The HSM20 is the HSM10 with two set-points instead of one. Two potentiometers are adjusted independently, so you can set a low threshold that raises a warning and a second threshold that trips the plant, from the same probe. Three indicator states — red below the first set-point, yellow above the first, green above the second — let an operator read the flow band from across the room without a display or a control system. The all-in-one sealed construction is rated IP68 rather than IP67, so the body survives washdown and temporary flooding. It uses the same thermal-dispersion principle and the same treated 316L probe as the rest of the range, which means the same immunity to fouling and the same absence of moving parts.
Typical applications
- Cooling circuits needing both a warning and a shutdown threshold
- Pump protection where a second stage must isolate the drive
- Process lines with a minimum-flow alarm and a no-flow trip
- Machine tools with independent coolant and lubrication monitoring
Not certain HSM20 is the right unit?
Send the medium, range, process connection and the signal your control system accepts. We will confirm the model — or tell you which one fits better — before you commit to an order.
Same family
Other flow instruments
Illustrative imageThermal Flow Switch
Single set-point
Thermal-dispersion flow switch with a single adjustable set-point, sealed all-in-one stainless body rated IP67 and 100 bar. Relay, PNP, NPN or 4–20 mA output, G1/2 thread as standard. No paddle and no moving part in the flow path, so scale and debris cannot jam it.
View specifications
Illustrative imageDigital Thermal Flow Switch
LED display
Thermal flow switch with a four-digit LED display showing live flow velocity, set by two front-panel keys rather than a screwdriver. Reverse-polarity, short-circuit and overload protected. Handles media up to 100 °C and pressures to 100 bar, sealed to IP67.
View specifications
Mass Flow Controller
Closed loop, 100–200 L/min
Closed-loop gas flow controller combining a thermal flow sensor and a normally-closed solenoid valve in one body. Three ranges — 100, 150 and 200 L/min — with ±1 % FS accuracy, 2 s response and 5–100 % control range. Swagelok or VCR fittings, ±15 V DC supply.
View specifications