Specifying an instrument without a sales call
Three things decide most sensor orders: the measuring principle, the output signal your panel accepts, and the environmental rating. These pages cover all three, so an enquiry can start from a shortlist rather than a blank page.
Reference · Output signals
Which output do you need?
The output is usually the first thing to fix, because it decides what the control system has to do with the measurement — and whether you need a control system at all.
| Signal | When to use it | What to watch | Where it appears |
|---|---|---|---|
| Dry contact / relay | Switching a pump, valve, alarm or interlock directly. No controller required. | Relay contacts have a finite switching life; a contact rated 1 A will not start a 5 A motor without a contactor. | HWS, HLS, HTS float and magnetic switches, flow switches, pressure controllers |
| PNP / NPN | Machine control — PLC digital input, conveyor logic, OEM equipment. | Sinking versus sourcing is not interchangeable. Order the type the input card expects. | HSM flow switches, UB ultrasonic sensors, HSM41 laser displacement |
| 4–20 mA (2-wire) | Long cable runs into a PLC analogue card or DCS. Immune to volt-drop over distance. | The loop needs a minimum supply voltage that rises with the total loop resistance. | PDD pressure transmitters, HPS submersible level, TPT temperature transmitters |
| 0–10 V / 1–5 V | Short runs inside a cabinet, or into a controller with voltage inputs. | Voltage signals degrade over distance and pick up noise. Keep the run short. | Selected transmitters and displacement transducers |
| RS485 Modbus RTU | Multiple instruments on one pair of wires into a PLC, gateway or SCADA. | Every device needs a unique address on the bus, and the bus needs termination at both ends. | HPS submersible level, TPT100, edge gateway, power meter |
| Wireless — 4G / LoRa / NB-IoT | Sites with no mains power and no cable route: pipelines, reservoirs, heating networks. | Battery life depends on reporting interval and signal strength; confirm both before sizing. | Wireless pressure, temperature, level and gas instruments |
Scroll the table sideways to read all four columns.
Reference · Level measurement
Six level principles, and when each one fails
Level is the widest part of the catalogue because no single principle suits every tank. The column that matters is the second one — the conditions where each principle is the wrong choice.
Float switch
- Good for
- A discrete point — pump start/stop, high alarm. No power needed for the switch itself.
- Avoid when
- Continuous measurement. Sticky media that will not release a float.
Magnetic flip-column gauge
- Good for
- Local indication with no electronics at all, plus an optional 4–20 mA transmitter on the same column.
- Avoid when
- Media that crystallise on the column, and narrow ranges where resolution is poor.
Magnetostrictive transmitter
- Good for
- Continuous 4–20 mA or RS485 over 3–5 m with no moving parts in the vessel.
- Avoid when
- Foam and vapour that confuse the float, unless the float is specified for it.
Hydrostatic (submersible)
- Good for
- Deep wells and reservoirs. Rated IP68, so permanent immersion is fine.
- Avoid when
- Vessels under pressure, and media with varying density — head is not level.
Capacitive
- Good for
- Viscous and coating media, and aggressive chemistry where a contact probe survives better.
- Avoid when
- Build-up that changes the dielectric, unless the probe is specified for it.
Microwave through-wall
- Good for
- Foam, build-up or aggressive chemistry where even a coated probe is a liability.
- Avoid when
- Thick or metallic vessel walls between sensor and medium.
Reference · Environmental rating
Reading an IP code
The first digit is solids, the second is water. The catalogue ratings below are the ones that appear across the product range; a higher number is not automatically better if the installation never sees water.
Note that IP68 requires a stated depth and duration — an IP68 claim without those two numbers is not meaningful.
- IP65
- Dust-tight; protected against water jets from any direction.
- IP67
- Dust-tight; protected against temporary immersion to 1 m for 30 minutes.
- IP68
- Dust-tight; protected against continuous immersion at a stated depth and duration.
Documentation
Datasheets, drawings and certificates
The specification tables on every product page are the current published data. For a purchase, an installation or an import file you usually need the document underneath it — the PDF datasheet for the exact model, a dimensioned drawing, or the certificate scans. Those are issued per request rather than posted publicly, because the revision has to match the unit you are buying.
PDF datasheet
The current revision for the model, in English.
Dimensioned drawing
For installation clearance and connection layout.
Calibration / test record
For the individual unit, where the project requires it.
CE / ISO / RoHS scans
For import and tender files.
Material certificate
Wetted-part material traceability on request.
Selection shortlist
Two or three candidate models against your process conditions.
Browse by family
- Flow Sensors & Switches4
- Level Sensors & Transmitters17
- Pressure Transmitters & Controllers6
- Temperature Sensors & Transmitters10
- Ultrasonic Proximity Sensors7
- Laser Methane Detection3
- Linear Displacement Transducers5
- Analytical Instruments3
- Industrial IoT & Wireless Sensing5
- Motion, Photoelectric & Metering6
Need a model that is not in the catalogue?
Send us the medium, range, thread and output you need. Most custom configurations are quoted from the factory engineering desk rather than handed to a trading partner.