Level Sensors & Transmitters
HCT40 Capacitive Level Controller
2 relays

HCT40 technical data
Measurement
- Measuring range
- 100–5000 mm
- Sensor type
- Coaxial capacitance
- Accuracy class
- 0.2 or 0.5
- Sampling rate
- 4 readings per second
- Display range
- −1999 to 9999
- Long-term stability
- 0.5 % FS/year
Electrical
- Supply voltage
- DC 24 V, AC-DC 110 V, AC-DC 220 V
- Power consumption
- ≤ 3 W
- Analogue output
- 4–20 mA / 0–10 or 20 mA / 0–5 or 1–5 V DC
- Relay outputs
- 2 pairs
- Relay rating
- 5 A at 250 V AC, 5 A at 30 V DC
- Relay life
- > 100 000 operations
- A/D conversion
- 24-bit
Mechanical
- Ambient temperature
- −20 to +70 °C
- Medium temperature
- −20 to +80 °C
- Storage temperature
- −40 to +100 °C
- Relative humidity
- 0–80 %
- Housing material
- Plastic or aluminium alloy
- Probe material
- Stainless steel
- Connection
- G1/2, M20×1.5 or to order
- Ingress protection
- IP65
Values are for the standard configuration. Ranges, threads, probe lengths and output types outside this table are available on request — the datasheet revision for a custom build is issued with the quotation.
Request the PDF datasheet →Level Sensors & Transmitters
HCT40Capacitive Level Controller
2 relays
Coaxial capacitive level controller with two relay outputs, LED display and 24-bit A/D. 100–5000 mm, 4–20 mA / 0–10 V / 1–5 V selectable, stainless probe. The compact option for simple high/low control on viscous media.
Engineering reply · Evaluation samples available · Custom ranges built to order
- Two relay outputs for simple high/low duty
- No moving parts, suits coating media
- Range 100–5000 mm
- Plastic or aluminium housing
- Selectable analogue output
How it works
A two-relay version of the capacitive controller for duties that only need high and low: fill-and-drain on a small tank, high-level alarm plus low-level cut-out on a day tank. The measuring element is identical to the HCT100, so the same suitability for viscous and coating media applies, and the plastic or aluminium housing is lighter where the instrument is bracket-mounted rather than panel-mounted.
Typical applications
- Day tanks and small mixing vessels
- High-level alarm with low-level pump cut-out
- Coating and viscous product level
Not certain HCT40 is the right unit?
Send the medium, range, process connection and the signal your control system accepts. We will confirm the model — or tell you which one fits better — before you commit to an order.
Same family
Other level instruments

Capacitive Level Controller
5 relays, RS485
Coaxial capacitive level transmitter and controller, 100–5000 mm, with 24-bit A/D, five relays, RS485 Modbus and selectable analogue output. Handles viscous and coating media where float instruments would seize. 316 stainless probe.
View specifications
Rod Float Level Switch
1–4 set-points
Discrete level switch with one to four magnetic reed points on a stainless guide rod. Passive dry contacts need no power supply, and the reed elements never touch the liquid. Rod diameter 9–25 mm, pressure to 6.3 MPa, temperature to 150 °C.
View specifications
Rod Float Level Switch
Extended body
The HWS20 shares the HWS10's reed-on-rod principle with a longer, heavier-duty body for deeper tanks and wider mounting spans. Same passive dry-contact output, 1–4 set-points, 6.3 MPa and 150 °C ratings.
View specifications
Illustrative imageCable Float Level Switch
SPDT, 15 A
Injection-moulded float on a flexible rubber cable, switching 15 A at 250 V AC through an SPDT contact. Suits long cable runs, multiple points on one drop, submersible pumps and media carrying granular solids. IP68, specific gravity above 0.6.
View specifications